Main characteristics of submerged arc furnace transformers
Continuous, stable, and high load rate:
The smelting process is uninterrupted 24 hours a day. The transformer operates at or close to the rated load for a long time, pursuing extremely high operating efficiency and reliability. This is completely different from the periodic impact load of arc furnaces.
Extremely low secondary voltage and extremely high secondary current:
In order to concentrate energy inside the furnace charge and avoid heat loss and damage to the furnace lining caused by excessively long arcs, submerged arc furnaces adopt "submerged arc" or "subsurface arc" operations. This requires a very low secondary operating voltage (usually tens to hundreds of volts), which results in an astonishing secondary current (up to tens of thousands to over 100,000 amperes).

Special impedance requirements:
Sufficient impedance is needed to limit short-circuit currents, though not to the extreme levels pursued in refining furnace transformers. The impedance value (typically between 6% and 12%) must match the charge resistance for optimal energy input.
Importance of three-phase balance:
The balance of current and resistance among the three-phase electrodes is directly related to the stability of furnace conditions, product quality, and energy consumption. The design of the transformer and short network system must ensure three-phase balance as much as possible.
Imposing a huge fundamental wave load on the power grid:
Submerged arc furnaces are "big electricity consumers" of the power grid, with a usually low power factor (natural power factor is about 0.65-0.8), and must be equipped with large-scale reactive power compensation devices.

Application and selection points
Process matching first:
Transformer parameters (especially the secondary voltage range) must be strictly matched and calculated with process parameters such as furnace type, product variety, raw material characteristics, and electrode diameter.
The "short network" is an extension of the system:
The impedance and balance of the section from the secondary outlet end of the transformer to the electrode (called the "short network") have an impact on the furnace condition that is almost as important as the transformer itself. The transformer and the short network (copper bars, water-cooled cables, conductive jaws, etc.) must be designed as an integrated electrical system.

Reactive power compensation and harmonic control:
Large-scale dynamic reactive power compensation and filtering devices such as TCR/TSC type SVC or FC must be equipped to improve power factor, stabilize grid voltage, and absorb harmonics.
Absolute reliability of the cooling system:
Any cooling interruption may cause a catastrophic accident within one or two minutes.
Quality control:
The manufacturing process, insulation treatment, and outlet structure of high-current windings are the keys to quality and service life.

We have mature experience in manufacturing submerged arc furnace transformers. In response to the requirements of fully enclosed smelting, for transformer products with a capacity of 15,000 kVA and above, we design them as single-phase transformers with a structure featuring water-cooled tube (adjustable copper tube) side outlet, on-load voltage regulation, and unified cooling. For large-scale on-load voltage regulation and 110kV class products, we adopt "8"-shaped coils that are all wound and formed in one go, which enhances coil strength and reduces eddy current loss. For transformer oil tanks, we prioritize the use of folded plate type, minimize weld seams as much as possible, and strictly conduct positive and negative pressure tests to ensure the reliability of product sealing.

Reference parameters for submerged arc furnace transformer HTDFPZ-13500/110 produced by our company
| Parameter Item | Parameter Value |
| Frequency | 50 Hz |
| Input Voltage | 110 kV |
| Output Voltage | 100-185-270V |
| Phase | Single |
| Coil Number | Two Windings |
| Type | Oil-Immersed Transformer |
| Product name | Single Phase Oil Immersed Transformer |
| Rated capacity | 13500KVA |
| Cooling Method | OFAF |
| Standard | GB1094,GB/T6451 |
| Connection symbol | Dd0/ Ii0 |
| Material | Silicon Steel Sheet |
| Winding Material | Copper 100% |
| Warranty | 12 Months |
Reference parameters of submerged arc furnace transformer HTDSPZ-16000/110 produced by our company
| Parameter Item | Parameter Value |
| Frequency | 50 Hz |
| Input Voltage | 110 kV |
| Output Voltage | 100--185-270V |
| Phase | Single |
| Coil Number | Two Windings |
| Type | Oil-Immersed Transformer |
| Product name | Single Phase Oil Immersed Transformer |
| Rated capacity | 16000KVA |
| Cooling Method | OFWF |
| Standard | GB1094,GB/T6451 |
| Connection symbol | Dd0/ Ii0 |
| Material | Silicon Steel Sheet |
| Winding Material | Copper 100% |
| Warranty | 12 Months |